Today I want to show you something we're working on at PROTELECTSA: connecting RTC2 to the FREJA 300 test set (PROGRAMMA / Megger).


RTC2 4.0 FREJA 300 Tests window with the frequency vs. trip time plot and four measured points
RTC2 4.0 FREJA 300 Tests window with the frequency vs. trip time plot and four measured points

The idea is for those who already have a FREJA 300 test set to run their tests from RTC2 and see the results on their relay curves. Report integration is still in development.


How it works:

RTC2 talks to the test set through the COM port (RS232) and puts it in remote mode. You load the relay settings and the test points; with "Run all", the test set injects, RTC2 measures the trip time and marks each point as within or outside tolerance against those settings. Each point appears on the curve as the test runs, and everything is kept in a live log.


What the video shows, with a real relay:

  • The relay settings loaded into RTC2 and the 50/51 curve plotted

  • The new "FREJA 300 Tests" window, with one tab per function 50/51: the measured points on the curve

  • 81: frequency vs. trip time

  • 27: trip within tolerance


Development status:

  • 50/51 and 81: tested with a real relay.

  • 27/59: under testing. Pending: report integration and the remaining functions (67, 25, 21, 32 and 87).

  • This is a development preview, with no release date.

  • Equipment used in the video: PROGRAMMA FREJA 300.


I'd like your input: which function should be integrated first? And how do you currently document your secondary-injection test results? Write to me at: info@protelectsa.net